the median / average value from the OWS. The out puts of the transmitter shall be con tinuously monitored for

excessiv deviation, which shall be displayed, logged & alarmed. . Dual measurement scheme for analog inputs employing two independent transmitters,

connect ed to separate tapping points shall be employed for the remaining measur ements used in CLCS and TCS. he

output of the redundant transmi tters shall be continuously moni tored for excessive deviation. In case the deviation is within

limits , the mean value shall be used for the control loop. If the deviation beco mes high, the loop shall be automatically ransferred to manual. However, if one 1 of 1 INDRADHANUSH GAS GRID LIMITED TECHNICAL SPECIFICATION FOR NATURAL GAS COMPRESSOR STATION FOR NORTH EAST GAS GRID PIPELINE PROJECT TS NO.: MEC//2UU/0/2/0 Control & Instru mentation (&) Chapter-0.0 2, MECON Limited, All Right Reserved Page 9 of 1 transmitter fails and the other transmitter remains healthy, th en the output of the healthy tr ansmitter shall be sed of the control. If the other transmitter also fails, loop shall trip to manual. The ou tput of the transmitters shall be continuous ly monitored for extensive oper ation, which shall be displayed and logged and alarmed. . For binary and analog inputs required in FPS and TPS, triple se nsing devices shall be provided. For cr itical binary and analog input required in OLCS / CLCS / TCS which are equired for equipment protectio of more than one equipment (.. flame failure, Deaerator level ve ry low etc), triple sensing devices sha ll be provided. For other criti cal binary and analog inputs required in OLCS / CLCS / TCS for protection and interlock purpose also (.. thos interlocks which may result in loss of generation, non-availability of major equipment etc.), dual ensors shall be provided. . The signal conditioning functions like, multiple measurement sc hemes, square root extrac