partmentalized construction confirming to loss of service co ntinuity of LSC2B and shall have separate compartments for VCB, bus bars,

Ts and outgoing cables and meteri ng & protection devices. Each HT compartment shall be isolated to confirm to internal

ar compliance requirement. Switchboard shall be extensible on both sides. Minimum panel width shall be 8 mm upto 1kV switchboard

All supporting insulators in bus chamber shall be easily access ible with detachable covers for easy replacement. CTs shall be

located in such way that that they are easily ac cessible from rear of the panel. Removable lifting arrangement for each transport unit shall be provided. Doors shall be provided with padlocking provision and the door shall not be forming part of the draw-out truck 1 of 1 INDRADHANUSH GAS GRID LIMITED TECHNICAL SPECIFICATION FOR NATURAL GAS COMPRESSOR STATION FOR NORTH EAST GAS GRID PIPELINE PROJECT ______________________________________________________________________________________________ TS NO.: MEC//2UU/0/2/0 Electrical system Chapter-0.0 2, MECON Limited, All Right Reserved Pag 3 of 2 Separate back covers with handles shall be provided for bus cha mber, and cable chamber. The back cover shall be necessarily in two parts for easy handling. Independent explosion vent shall be provided for each HT compartment . CB chamber, bus chamber, cable chamber to compl to the internal arc requirement Earthed metallic barriers between compartments and between vert ical sections of adjacent panels shall be ensured. Control cables entry shall be from bottom nd on front side. & ng feeders shall be provided. Suitable slotted channel shall be provided in the cable chamber for clamping the cable for support. The controls, indicating lamps , relays and meters shall be m