ntegrati on to vendor independent SCADA/ Automation system. For protective relays, the scope shall include the following : ) Necessary

software and hardware to up /down load the data to/fr om the relay from/to the laptop loaded with all necessary

software. ) Incomers, Buscouplers and all outgoing feeders shall be provid ed with relay having Graphical Display unit. ) The

relays should have front and rear ports for communication .. Front network port for local communica tion for relay settings,

modifi cations, extraction and analysis of fault/event/ disturbance records fro laptop and Rear fiber optic/ Copper port on IEC6 standard for remote ommunication to SAS system. ) The relays shall have the follo wing tools for fault diagnostics 1. Fault record: The relay shall have the facility to store fault records with information on cause of trip, date, time, trip values of electr ical parameters. 1 of 1 INDRADHANUSH GAS GRID LIMITED TECHNICAL SPECIFICATION FOR NATURAL GAS COMPRESSOR STATION FOR NORTH EAST GAS GRID PIPELINE PROJECT ______________________________________________________________________________________________ TS NO.: MEC//2UU/0/2/0 Electrical system Chapter-0.0 2, MECON Limited, All Right Reserved Pag 3 of 2 2. Event record: The relay shall have the facility to store at lea st 1 time stamped event records with 1ms resolution. 3. Disturbance records: At least 3 secs of disturbance records ith 1 recording shall be provided in the offered Numerical relays. Ea ch record shall store data from all the analogue channels, at leas 1, used at least 3 digital channels. he data from DR function shall be vailable in IEEE format. ) All relays shall be flush mount ed in dust proof cases and shall be mounted on front fascia of control cubical. ) All protective relays shall be in draw out or plug-in type or ith plugin terminals, m