st the entrance of the moisture and, provision to maintain the constant pressur in the cable. * Cold Shrink Cable

Joints shall be used in Hazardous Area. ) For LT Power and control cable The cables shall be terminated in

accordance with relevant conn ection diagram. Termination and clamping shall be carried out in such manner as to avoid strain

on the terminals. Glanding shall be done for direct entry of both power and contr ol cables into the panels/

enclosures by the contractor. Double Compression type brass ca ble glands shall be used. Crimping type tinned copper lugs only shall be used for all cable termination All power& control cable termina tions shall be by means of crim ping type cable lugs. For flexible conductors, solder ed termination shall be adopted. In case of aluminium power cables termination on copper bus bars, suitable aluminium copper bimetallic washers shall be used. Corrosion inhibiting grease shall be use for aluminium cable terminations. Cold Compound Cable Joints shall be used for LT Power & Control Cablein Hazardous Area. ) Exposed & Concealed conduits Exposed conduits shall be laid alo ng walls, floors, ceilings, on steel supports etc. as per working drawings/site requireme nts in consultation with the supervisory personnel. The conduits shall be neatly run and evenly spaced. Fixing of conduits to the supports on wall, column, structure hall not be done by welding. Exposed conduits shall be adequately supported by rack , clamps, straps etc. Jointing of conduits shall be done only in straigh portion and not in bend portion. The contractor shall have arrange ments at site for bending faci lities for conduits as well 1 of 1 INDRADHANUSH GAS GRID LIMITED TECHNICAL SPECIFICATION FOR NATURAL GAS COMPRESSOR STATION FOR NORTH EAST GAS GRID PIPELINE PROJECT ______________________________________________________________________________________________ TS NO.: MEC//2UU/0/2/0