Transformer for 2V AC Sockets 1.0 Type Dry type Step-down transformer Air-coole 2.0 Ratin Minimum 2VA 3.0 Primary / secondary

volta ge 2V /2.5 AC , single-phase 4.0 Construction The transformer shall be enclosed in industria wall mounting stainless steel

(2 mm thick) box having separate chambers for the transformer, incomin and out going MCBs. 5.0 Cable entry Suitable knock-out

shall be provided at the to and bottom for cable entr throu gh GI pipes. 6.0 No. of windin Two

windin 1 of 1 INDRADHANUSH GAS GRID LIMITED TECHNICAL SPECIFICATION FOR NATURAL GAS COMPRESSOR STATION FOR NORTH EAST GAS GRID PIPELINE PROJECT ______________________________________________________________________________________________ TS NO.: MEC//2UU/0/2/0 Electrical system Chapter-0.0 2, MECON Limited, All Right Reserved Pag 1 of 2 7.0 Protection SPN MCBs on primary and secondary side incorporatin overload and short circuit releases. 8.0 Utilit Power suppl to 2V repair networ 9.0 Locatio On structural platforms 1.0 2V SWITCH SOCKET OUTLET (For use at Shop Floors/Technological areas, Panel rooms, cable floors etc.) 1.0 Type 1 pole, 5 pin with third pin earthed industrial type receptacles . non-reversible, metal- lad, dust proof, industrial ype suitable for horizontal insertion. 2.0 Ratin 2 AC , 5+1A, 3.0 Construction Metal clad gaske tted construction, weatherproo All socket outlets shall be supplied with heavy- duty type plu and cap with chain. 4.0 Isolation Switch rotary type switch mounted flush in the so cket outlet box. The isolating switches shall be manually operated industrial ype of cate gory AC 2. 5.0 Protection Operating handle of the rotary switch shall be fixed in such manner that it shall not be possible either to inse rt or withdraw the plug without switchin off the suppl . 6.0 Cable entry Suitable for cable entry through 2mm dia. conduit. 7