s Pipes complete with connections, flanges, bends and tees etc. shall be supplied along with the system. 1 of 1

INDRADHANUSH GAS GRID LIMITED TECHNICAL SPECIFICATION FOR NATURAL GAS COMPRESSOR STATION FOR NORTH EAST GAS GRID PIPELINE PROJECT ______________________________________________________________________________________________ TS

NO.: MEC//2UU/0/2/0 Electrical system Chapter-0.0 2, MECON Limited, All Right Reserved Pag 6 of 2 5.2 Other items Oil drain

and nitrogen injection openings with gate valves on ransformer / reactor tank at suitable locations. Flanges with dummy piece in

conservator pipe between Buchholz elay and conservator tank for fixing TCIV. Fire detector brackets on tr ansformer tank top cover. Spare potential free contacts for activating the system .. in differential relay, Buchholz relay, Pressure Relief Device / RPRR, Circuit Breaker of transformer Pipe connections between transformer / reactor and FEC and betw een FEC and oil pit required for collecting top oil. Cabling for fire detectors ounted on transformer top cover Inter cabling between signal bo , control box and Fire Extinguishing Cubicle(FEC). Butterfly valves /Gate valves on oil drain pipe and nitrogen in jection pipe which should be able to withstand full vacuum. Supports, signal box etc. which are to be painted with enameled paint. 0.0.0 DRY TYPE DISTRIBUTION TRANSFORMER-RESIN CAST 1.0 TECHNICAL PARTICULAR Sl. No. Particulars Parameters 1. Type Cast resin encapsulated dry type, three phase, core type with circular concentric windings. 2. Application/ Duty Distribution 3. Continuous rating 6 kVA(minimum) 4. Voltage Ratio (HV/LV) 4.1 Primary voltage 6.6 kV 4.2 Secondary no load voltage 4V 5. Voltage Variation (HV/LV) As explained above 6. Control Voltage 1 DC 1 of 1 INDRADHANUSH GAS GRID LIMITED TECHNICAL SPECIFICATION FOR NATURAL GAS COMPRESSOR ST